Product description | |
| > Based on special flame-retarded resin in high strength,high-effective flame retardant, vesicant, polar solvent, addition agent … | |
| > Thin coat, less dosage, long time anti-fire, strong adhesion force. | |
| > Good resistance of climate, wind and water, good shock resistance and freeze-thaw resistance. | |
| > Good chemical atmospheric corrosion resistant. | |
| > The cover will expand and form thickening and symmetrical thermal-protective coating when meeting fire, expending the time of fire resistant to achieve the anti-fire purpose. | |
| > Widely used. Low temperature operating. | |
Recommended uses |
| > Anti-fire protection of bare steel structure as well as metal and other material structure of gymnasium, exhibiting hall, waiting hall, high-rise building, underground project and factory building. |
Capability of anti-fire and Theory dosage | ||||
The time of anti-fire (min) | 30 | 60 | 90 | 120 |
Coat thickness (mm) | 0.6 | 1.02 | 1.48 | 1.99 |
Coat area (kg/) | 1.08 | 1.55 | 2.68 | 3.60 |
Main performance: (Outdoors) | |
Test item | Technical target |
1. State in the container | Liquid in symmetrical and morbidezza without agglomeration after stirring |
2. Desiccation time(surface dry) | ≤8 hours |
3. Appearance and color | White |
4. Crack resistance of earlier drying | Without crackle |
5. Cohesional strength | ≥0.2 (Mpa) |
6. Hot and cold circulation resistant(times) | ≥720 |
7. Exposure hot resistant (h) | ≥504 |
8. Resistance to heat and humidity (h) | ≥15 |
9. Acid resistant (h) | ≥360 |
10.Alkali resistant (h) | ≥360 |
11. Salt fog resistance (times) | ≥30 |
Execution method |
| > The surface of steel structure should descaling achieve St3 level, and painting epoxy anti-corrosive primer firstly. |
| > Mix round uniformity before operation. Diluting by adding thinner (≤5%) if the paint is too thick to operation well. |
| > Operating by series. The thickness of first layer should not exceed 200um. Posterior thickness should not exceed 300um. Every operating interval should not less than 24 hours (23±2℃). |
| > Best operating environment: temperature.0~35℃, relative humidity85%. |